The FCI 7100 series fire alarm control panel is a
multi-processor-based, analog addressable system in a
compact, yet expandable, platform. Intended for
commercial, industrial and institutional installations,
it. is ideal for life safety and property protection
applications. The basic 7100 series control panel provides two analog
addressable signaling line circuits (SLCs). Each SLC
supports up to 99 analog addressable sensors, as well as
up to 99 addressable monitor modules and/or control
points. With 198 addresses available on each SLC, total
system capacity reaches 396 addresses. The 7100 uses an
advanced protocol that ensures an almost instant
response to events while at the same time suppressing
nuisance alarms.
The system may be programmed with either the
Windows®-based Field Configuration Program (FCP-7100) or
through a comprehensive set of intuitive, securely
password protected front-panel programming options. This
important feature allows the system to quickly adapt to
any future requirements brought on by changes in
occupancies, building remodelings, or other
contingencies.
The sophisticated circuitry and powerful analog
software enables the 7100 series fire alarm control
panel to read the specific sensitivity level of each
sensor and compensate for any changes due to age, dust accumulation or other
environmental factors. The 7100 incorporates the FCI
Listed Integrated Sensitivity Testing (LIST) which meets
NFPA 72 sensitivity testing and maintenance
requirements. The LIST testing allows substantial
savings in both maintenance and service while virtually
eliminating nuisance alarms.
The Model 7100-2D (non-FM) features an integral
Digital Alarm Communicator Transmitter (DACT) with all
popular transmission formats and a 16-digit telephone
number field. It is 8-digit Carrier Information Code (CIC) compliant
and also prevents dialer-runaway in the event of
intermittent system faults. The 7100-2D is UL Listed for
Remote Station, Proprietary, and Central Station fire
alarm systems.
The 7100 is housed in an attractive, contemporary
styled cabinet. It allows ample space for wiring and
room for batteries up to 7A/H capacity.
Features:
- Integral Digital Alarm Communicator (with the
7100-2D)
- 120 or 24O VAC (optional) Input Line Voltage
- 80.character Alpha-numeric Display Two Style 4
(Class "B") Signaling Line Circuits. Style 6 (Class
"A ") with optional CAOM module
- Two Style Y (Class "B") Regulated Notification
Appliance Circuits rated for 1.5 Amp. each. Style Z
(Class "A") with optional CAOM module
- Suitable for Pre-Action Deluge applications with
optional MCOM module
- Intuitive Front Panel Programming
- Periodic Trouble Reminder
- Individual Sensor Drift Compensation
- Listed Integral Sensitivity Testing (LIST)
- Dual-stage Maintenance alerts ("Dirty" and "Very
Dirty")
- Multi-level Sensor Sensitivity Adjustments (Front
Panel programmable)
- Day/Night Sensitivity Adjustments (Front Panel
programmable)
- Alarm Verification per Individual Sensor
- Positive Alarm Sequence for Sensors or Monitor
Modules
- Four Levels of System Access using Six Digit
Passwords with up to Five User Passwords per Level
- Duplicate and Extra Address indications
- March Time (60 or 120 BPM)/ Temporal Pattern/ Coded
Fours/ California Code
- User-Defined Zone Coding
- Cross Zoning
- 500 Event Log
- Fan Restart with Sequential Restart Delay
- Upload/Download of Panel Configuration between Panel
and FCP-7100 program (Password protected feature)
- Up to 64 7100 panels in NetSOLO® network with
optional INI-7100 module
|