Control Panel
The E3 Series® Expandable Emergency Evacuation System
by Gamewell-FCI is in the forefront of the latest
generation of fire alarm control panels. Employing the
new high-speed Velociti® sensors, the E3 Series provides
previously unattainable polling speed and response
together with the flexibility demanded by today’s
emergency evacuation systems. In addition to their
high-speed polling rate, the Velociti Series of sensors
feature bi-polar LEDs that flash green for normal
polling, and light red steadily to indicate an alarm.
The E3 Series is equipped with an 80-character LCD-E3
alphanumeric LCD display that allows 40 characters to be
user-defined for custom installations. Up to six (6),
keyboard LCD displays may also be remotely located. In
addition, you can install five of the familiar
LCD-7100/RAN-7100 remote displays. The displays show
instant system status information and can be connected
in any desired area of an installation.
A high-speed 32-bit processor easily tackles a wide
array of applications from small office buildings to
multi-complex, high-rise installations.
The (64) node networking is made possible by 625K
baud/ARCNET communications using twisted-pair copper
cable, fiber-optic cable, or a combination of both. In
addition, the Addressable Node Expander (ANX) board
expands the
network to one hundred and twenty-two (122) nodes.
The basic E3 Series is equipped with an
ILI-MB-E3/ILI95-MB-E3 Intelligent Loop Interface-Main
Board, ILI-S-E3/ILI95-S-E3 Intelligent Loop Interface
Expansion Board, ANX, and ASM-16 Addressable Switch
Module that features sixteen (16), software programmable
switches, each accompanied by red, green and yellow LEDs
that can be programmed to indicate operation of the
switches. Additional ASM-16 modules may be added to
expand the operation to a plateau previously unimagined.
The Intelligent Loop Interface - Expansion Board
(ILI-S-E3/ILI95-S-E3 provides the E3 Series control
panel with two (2), additional signaling line circuits.
The layout is similar to the ILI-MB-E3/ILI95-MB-E3 with
the exception that a number of components are omitted.
It occupies one node on the Broadband network.
Each ILI-MB-E3/ILI95-MB-E3 can support as many as
sixteen (16), ANU-48 LED Driver modules supporting
hundreds of LEDs on a 3rd party graphic annunciator for
remote annunciation. The ANU-48 modules may be installed
in any Listed remote annunciator. It can be remotely
located via an RS-485 serial interface. An array of
cabinets allows for neat, compact, attractive
installations.
Panel Features:
- IBC Seismic Certified
- Listed under UL® Standard 864, 9th Edition
- UL Listed for smoke control (dedicated and
non-dedicated) when properly configured
- FM/UL Listed for Pre-action/Deluge use
- Styles 4, 6, or 7* signaling line circuits
- Two to (244) SLCs each supporting 159 sensors
and 159 modules
- 625K baud ARCNET communications using wire,
fiber, or mixed configurations for installation
flexibility
- High-speed 32 bit processor and 4100 event
history log
- Advanced Boolean logic-based programming such as
AND, OR, NOT, time delay and calendar functions
configurable via computer programming
- Supports up to (16), ASM-16 addressable switch
or ANU-48 LED driver modules per
ILI-MB-E3/ILI95-MB-E3
- Two (2), Class A, Style Z or Class B, Style Y,
notification appliance circuits rated at 2.0 amps.
per circuit
- Integral city connection
- Flexible 115,200 baud high speed RS-232
interface
- 40 character user-defined text per device
- Supports up to five (5), LCD-7100/RAN-7100
displays and six (6), LCD-E3 keyboard displays per
ILI-MB-E3/ILI95-MB-E3
Velociti® Intelligent Service Features:
- Poll 318 devices in less than two (2) seconds
- Activate up to 159 outputs in less than five (5) seconds
- LED’s blink associated device address during Walk Test
- Fully digital, hi-precision protocol
- Up to 9 levels of sensitivity adjustment
- Pre-Alarm adjustable between 15 levels for both Alert and Action
- Day/night automatic sensing adjustment
- Sensitivity windows:
- Ion .05 to 2% obscuration
- Photo 1 to 3% obscuration
- Laser .02 to 2% obscuration
- MCS Acclimate2F .5 to 4%, also self-adjustable options 1 to 2%, 2 to 3%, 3 to 4%
- HARSH 1 to 3% obscuration
- Drift compensation
- Each Loop Card has its own integral
processor providing maximum survivability on loss of
any other component. SLC provides full response on
loss of any other system processor
- Optional programmable switches can be configured
to enable, disable or group any combination of
output devices
- Integrated point or Grouped Cross Zoning allows
for numerous devices installed at any location to
cooperate and determine alarm condition
- Automatic detector sensitivity testing
- DIRTY and VERY DIRTY detector maintenance alerts
Cabinets
The E3 Series® Expandable Emergency Evacuation System
by Gamewell-FCI offers several cabinet size options.
These cabinet options allow for neat, sturdy, attractive
installations. The E3 Series cabinet assembly is a
compact, wall-mounted enclosure. A typical cabinet
includes a backbox and an outer locking door. In
addition, there are several inner door choices and
mounting plates to accommodate a variety of E3
sub-assemblies.
Each cabinet backbox includes mounting
patterns for plates to aid the installer in arranging
and securing the subassemblies to the backbox. Backbox
knockouts are also positioned at numerous points to
allow a conduit access into the enclosure. Four (4)
Annunciator Cabinet sizes provide maximum flexibility
that can meet any application.
- Cabinet A or AA offers 2 slot and 3 slot options to
accommodate either of the following configurations:
- Cabinet A or AA, 2 slot allows space for one (1) LCD-E3 and one (1) NGA or one (1) ASM-16/ANU-48.
- Cabinet A1 or AA, 3 slot provides space for either one NGA and two ASM-16s or three ASM-16s/ANU-48s.
- Cabinet A1 houses one NGA or one ASM-16/ANU-48.
- Cabinet A2 accommodates a single LCD-E3 display.
E3BB-RBSlim or B-Slim contains the 600 Series cabinet.
Cabinet B includes a mounting plate that contains a
space for the ILI-MB-E3/ILI95-MB-E3, PM-9/PM-9G
sub-assemblies and batteries set inside the backbox.
Additional subassembly options mounted on the backbox include the DACT-E3 and
RPT-E3. The 2 slot inner door houses the following
options:
- one (1) LCD-E3 module and
- either one (1) ASM-16/ANU-48 or one (1) NGA module
Both C and D size Command Center cabinets house a
variety of E3 Broadband sub-assemblies in multiple
configurations that provide a solution to a wide
range of applications. Two (2), flexible inner
door panel selections are available for C and D size
Command Center cabinets that may contain a fire
fighter’s phone handset, a microphone, and optional
modules to meet the facility operation requirements.
Cabinet Features:
- IBC Seismic Certified
- 16-gauge steel backbox
- Removable outer and inner doors
- Inner door bonding strap used to provide electrical
continuity for grounding
- Backbox and door ground studs provide positive
grounding. 180° opening door with full clearance
- Available in either black or red
- Lexan® windows appear on the doors of most cabinets,
except the Cabinet “C” and “D” INX cabinets and the
INX CAB-B cabinet which contain louvered doors
- 90° opening door with zero clearance
- Keylock with quarter turn latch
- Trim Ring accessories available
|
|
|
|
| |
| Manufacturers